logo
Henan Hongtai HVAC Equipment Co., Ltd.
Products
Products
Home > Products > Industrial Water Chiller > Midea Air Cooled Scroll Chiller Range 340-920kW for Commercial and Industrial Use Reliable Scroll Compressor Technology in Large-Capacity Air Cooled Configurations

Midea Air Cooled Scroll Chiller Range 340-920kW for Commercial and Industrial Use Reliable Scroll Compressor Technology in Large-Capacity Air Cooled Configurations

Product Details

Place of Origin: China

Brand Name: OEM; MIDEA

Certification: CB, ISO

Payment & Shipping Terms

Get Best Price
Highlight:

Midea air cooled scroll chiller

,

commercial industrial water chiller

,

large capacity air cooled chiller

Product Name:
Air Cooled Scroll Chiller
Cooling Operating Range:
0 To 48°C
Heating Operating Range:
-15 To 48°C
Cooling Capacity:
319.9-860 KW 340-920 KW
Model Range:
90-240 HA 100-260 HA
Refrigerant:
R410A
Type:
Heat Pump / Cooling Only
Product Name:
Air Cooled Scroll Chiller
Cooling Operating Range:
0 To 48°C
Heating Operating Range:
-15 To 48°C
Cooling Capacity:
319.9-860 KW 340-920 KW
Model Range:
90-240 HA 100-260 HA
Refrigerant:
R410A
Type:
Heat Pump / Cooling Only
Midea Air Cooled Scroll Chiller Range 340-920kW for Commercial and Industrial Use Reliable Scroll Compressor Technology in Large-Capacity Air Cooled Configurations
Midea Air Cooled Scroll Chiller Range 340-920kW
High-capacity air cooled chillers designed for commercial and industrial applications, featuring reliable scroll compressor technology in large-capacity configurations.
Product Overview
The Midea Air Cooled Scroll Chiller range provides comprehensive cooling and heating solutions for substantial commercial and industrial facilities. Available in two distinct configurations: the high-capacity RHAE/RCAE series (90-240HA, 319.9-860kW) and the standard RHAG/RCAG series (100-260HA, 340-920kW), with both heat pump and cooling-only models to meet diverse operational requirements.
These advanced units incorporate hermetically sealed scroll compressors with Intermediate Discharge Valve (IDV) functionality, optimizing compression efficiency during partial load conditions commonly encountered in commercial buildings. The shell-and-tube water heat exchanger design delivers measurable efficiency improvements compared to standard configurations, while electronically controlled expansion devices ensure precise refrigerant flow management.
Intelligent fuzzy-logic based defrost management monitors actual weather patterns to determine defrost necessity, maintaining heating capacity even when outdoor temperatures drop to -15°C with capacity reduction limited to below 38%. Multiple units can be combined through a dedicated parallel protocol supporting up to 8 machines, while optional heat recovery modules generate 40°C or 55°C domestic hot water. Integrated pump packages simplify hydraulic connections, and optional acoustic treatment reduces sound output for noise-sensitive installations.
Core Features & Benefits
  • Hermetic Scroll Compressors with IDV Control for optimized partial load efficiency
  • Shell-and-Tube Water-Side Exchanger delivering measurable efficiency improvements
  • Electronically Actuated Expansion Device for precise refrigerant management
  • Weather-Adaptive Defrost System maintaining heating output through cold periods
  • Limited capacity reduction (below 38%) when outdoor temperature reaches -15°C
  • Dedicated parallel protocol supporting up to 8 connected units
  • Optional heat recovery module providing 40°C or 55°C domestic hot water
  • Optional integrated pump assembly streamlining hydronic connections
  • Variable capacity output responding to actual building load conditions
  • Optional acoustic treatment package for noise-sensitive installations
Typical Applications
  • Regional shopping centers and mixed-use commercial complexes
  • Corporate office parks and business districts
  • Inpatient medical facilities and outpatient clinics
  • Manufacturing plant process temperature control
  • Pharmaceutical research and quality control laboratories
  • Cellular network equipment housing
  • Sports stadium audience comfort systems
Certifications & Standards
AHRI 550/590 – Performance and methods of test for water-chilling packages
Eurovent – European certification program for HVACR equipment performance
Technical Specifications
Parameter RHAE / RCAE (High Capacity) RHAG / RCAG (Standard)
Type Heat Pump / Cooling Only Heat Pump / Cooling Only
Cooling Capacity 319.9-860 kW 340-920 kW
Model Range 90-240 HA 100-260 HA
Refrigerant R410A R410A
Compressor Type Hermetic Scroll with IDV Hermetic Scroll with IDV
Heat Exchanger Shell-and-Tube Shell-and-Tube
Cooling Operating Range 0 to 48°C 0 to 48°C
Heating Operating Range -15 to 48°C -15 to 48°C
IPLV (AHRI 550/590) 4.7-4.8 4.7-4.8
Heat Recovery (Optional) 40°C / 55°C DHW 40°C / 55°C DHW
Modular Connection Up to 8 units Up to 8 units
Similar Products