The drain pipe is the part that ruins the ceiling.
Ask an installer what they remember about a recovery ventilator and they will rarely mention efficiency. They will mention the drain.
A conventional heat exchanger condenses. Moisture from the exhaust stream collects on the core, drips into a pan, and the pan needs a slope, a trap, a route to a floor drain and, in most buildings, a hole in a ceiling that somebody has to justify to the architect. On a hotel floor with forty rooms, that is forty drainage points, forty chances for a blocked trap, and one leak that ends up on a guest's ceiling.
Six of the eight models in the DC series do not need a drain at all. That single fact changes how the equipment is installed, and it is worth understanding why it is possible rather than taking it on trust.
The core is a chemically treated paper exchanger. Moisture passes through it as vapour rather than condensing on the surface, so the exhaust stream leaves carrying its humidity instead of depositing it inside the casing.
This works up to 1,000 m³/h. Above that, the physical scale of the core changes the behaviour and the 1,500 and 2,000 m³/h models require a PVC condensate connection.
The practical consequence is a ceiling void with no drain pipe, no trap, no slope and no fall to a floor drain. On the 200 to 1,000 m³/h models, installation reduces to three actions: hang the unit, connect the ducts, connect single-phase power. Nothing else needs to be coordinated with the drainage trade, and there is no trap to go dry in a building that sits empty over a holiday.
Casing depth across the range runs from 272 mm to 685 mm, and it steps with airflow rather than staying constant.
| Airflow band | Models | Casing depth |
|---|---|---|
| 200 to 400 m³/h | HRV-D200, D300, D400 | 272 mm |
| 500 to 1,000 m³/h | HRV-D500, D800, D1000 | 390 mm |
| 1,500 to 2,000 m³/h | HRV-D1500, D2000 | 615 to 685 mm |
The 272 mm casing is the number that matters in residential and hotel work, where a suspended ceiling is often 300 mm below slab. Three models fit that void with clearance for the hangers. The 390 mm models suit a 450 mm ceiling or a service corridor, and the two largest units belong in a plant room rather than a corridor ceiling.
Length and width matter as much as depth on the larger units: the 2,000 m³/h model is 1,811 mm long and 1,575 mm wide, which is a plant room footprint, not a ceiling void. Check the access route before the unit arrives, not after.
Duct spigot sizes step with airflow and are circular up to 1,000 m³/h, then rectangular.
| Models | Spigot |
|---|---|
| D200, D300 | 144 mm |
| D400 | 198 mm |
| D500, D800, D1000 | 244 mm |
| D1500, D2000 | 346 x 326 mm |
External static pressure ranges from 90 Pa on the smaller units to 200 Pa on the 2,000 m³/h model. That is the budget available for ducts, bends, filters and grilles, and it is the number to design against. A unit selected on airflow alone, with a duct run that eats 180 Pa, will deliver less air than the schedule says and the installer will be the one explaining it.
All models carry three fan speeds, so a marginal duct run can be recovered by moving up a speed. It costs power, not rework.
The bypass damper opens when outdoor temperature is below indoor temperature, sending incoming air around the core instead of through it. In shoulder seasons this provides free cooling with no compressor running.
The operating range is -7 °C to +43 °C outdoor and indoor, with indoor humidity below 80 percent. Below -7 °C, the unit is outside its declared envelope, and projects in colder climates need a pre-heat strategy rather than a bigger ventilator. This is a design decision, not an installation detail, and it is better settled at tender stage.
Every model is single-phase 220 to 240 V, 50 Hz, with a 3-core 2.5 mm² supply cable. Current draw runs from 0.64 A on the 200 m³/h model to 5.7 A on the 2,000 m³/h model, so a single dedicated circuit covers the smaller units and the largest ones need their own.
For export projects on other grid standards, the manufacturer supports OEM/ODM voltage customisation from 180 to 440 V at 50 or 60 Hz. That is a factory option, not a field modification, and it needs to be specified on the order.
This is where a ventilator stops being a standalone box and becomes part of a system.
The unit interlocks with Midea VRF indoor units and starts and stops with the air conditioning. When the floor is unoccupied and the VRF is off, the ventilator follows. That single link removes most of the wasted running hours on a typical office floor.
The KJR-27B/E wall controller covers five modes, four fan speeds including a sleep setting, and a timer, with up to 16 units on one controller. The WDC-120G/WK(A) adds CO2 display, filter status, group control, weekly scheduling, VRF interlock and delayed shutdown.
CCM-180A/WS(A) and CCM-270B/WS(A) bring ventilation and VRF under one interface across floors.
GW-MOD(A) delivers Modbus and IMMP-BAC delivers BACnet. Both present the unit as a clean set of points to the building management contractor, rather than as a proprietary device that needs a separate front end.
For a controls contractor, the useful question is not whether the unit supports a protocol but whether the point list is complete at handover. Confirm the gateway model on the order, because it is a factory-fitted option and not something that can be added later without a return visit.
| Model | Airflow | Dimensions L x W x H | Net / gross weight | Spigot | External static pressure | Condensate drain |
|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 1,195 x 801 x 272 mm | 53.6 / 70.6 kg | 144 mm | 100 Pa | Not required |
| HRV-D300(B) | 300 m³/h | 1,195 x 914 x 272 mm | 59 / 77 kg | 144 mm | 90 Pa | Not required |
| HRV-D400(B) | 400 m³/h | 1,276 x 1,204 x 272 mm | 71.5 / 91.5 kg | 198 mm | 100 Pa | Not required |
| HRV-D500(B) | 500 m³/h | 1,311 x 1,106 x 390 mm | 74.4 / 98.6 kg | 244 mm | 90 Pa | Not required |
| HRV-D800(B) | 800 m³/h | 1,311 x 1,286 x 390 mm | 80 / 104 kg | 244 mm | 140 Pa | Not required |
| HRV-D1000(B) | 1,000 m³/h | 1,311 x 1,526 x 390 mm | 90 / 112 kg | 244 mm | 160 Pa | Not required |
| HRV-D1500(B) | 1,500 m³/h | 1,740 x 1,375 x 615 mm | 181.5 / 213 kg | 346 x 326 mm | 180 Pa | PVC required |
| HRV-D2000(B) | 2,000 m³/h | 1,811 x 1,575 x 685 mm | 208.5 / 245 kg | 346 x 326 mm | 200 Pa | PVC required |
All models: single-phase 220 to 240 V, 50 Hz, 3-core 2.5 mm² supply cable. Operating range -7 °C to +43 °C, indoor humidity below 80 percent.
Filters wash or vacuum clean. The core should be vacuumed roughly every two years and must never be washed with water, because the treatment that allows vapour transfer is not designed to survive it. Fans are checked every six months. A differential pressure sensor monitors filter resistance and raises a reminder through the controller before airflow drops, so the schedule is driven by condition rather than by calendar.
Send us the ceiling void depth, the duct route and the destination country. We will confirm the model, the spigot size, the static pressure margin and whether the gateway you need is factory-fitted, before the order is placed.
The drain pipe is the part that ruins the ceiling.
Ask an installer what they remember about a recovery ventilator and they will rarely mention efficiency. They will mention the drain.
A conventional heat exchanger condenses. Moisture from the exhaust stream collects on the core, drips into a pan, and the pan needs a slope, a trap, a route to a floor drain and, in most buildings, a hole in a ceiling that somebody has to justify to the architect. On a hotel floor with forty rooms, that is forty drainage points, forty chances for a blocked trap, and one leak that ends up on a guest's ceiling.
Six of the eight models in the DC series do not need a drain at all. That single fact changes how the equipment is installed, and it is worth understanding why it is possible rather than taking it on trust.
The core is a chemically treated paper exchanger. Moisture passes through it as vapour rather than condensing on the surface, so the exhaust stream leaves carrying its humidity instead of depositing it inside the casing.
This works up to 1,000 m³/h. Above that, the physical scale of the core changes the behaviour and the 1,500 and 2,000 m³/h models require a PVC condensate connection.
The practical consequence is a ceiling void with no drain pipe, no trap, no slope and no fall to a floor drain. On the 200 to 1,000 m³/h models, installation reduces to three actions: hang the unit, connect the ducts, connect single-phase power. Nothing else needs to be coordinated with the drainage trade, and there is no trap to go dry in a building that sits empty over a holiday.
Casing depth across the range runs from 272 mm to 685 mm, and it steps with airflow rather than staying constant.
| Airflow band | Models | Casing depth |
|---|---|---|
| 200 to 400 m³/h | HRV-D200, D300, D400 | 272 mm |
| 500 to 1,000 m³/h | HRV-D500, D800, D1000 | 390 mm |
| 1,500 to 2,000 m³/h | HRV-D1500, D2000 | 615 to 685 mm |
The 272 mm casing is the number that matters in residential and hotel work, where a suspended ceiling is often 300 mm below slab. Three models fit that void with clearance for the hangers. The 390 mm models suit a 450 mm ceiling or a service corridor, and the two largest units belong in a plant room rather than a corridor ceiling.
Length and width matter as much as depth on the larger units: the 2,000 m³/h model is 1,811 mm long and 1,575 mm wide, which is a plant room footprint, not a ceiling void. Check the access route before the unit arrives, not after.
Duct spigot sizes step with airflow and are circular up to 1,000 m³/h, then rectangular.
| Models | Spigot |
|---|---|
| D200, D300 | 144 mm |
| D400 | 198 mm |
| D500, D800, D1000 | 244 mm |
| D1500, D2000 | 346 x 326 mm |
External static pressure ranges from 90 Pa on the smaller units to 200 Pa on the 2,000 m³/h model. That is the budget available for ducts, bends, filters and grilles, and it is the number to design against. A unit selected on airflow alone, with a duct run that eats 180 Pa, will deliver less air than the schedule says and the installer will be the one explaining it.
All models carry three fan speeds, so a marginal duct run can be recovered by moving up a speed. It costs power, not rework.
The bypass damper opens when outdoor temperature is below indoor temperature, sending incoming air around the core instead of through it. In shoulder seasons this provides free cooling with no compressor running.
The operating range is -7 °C to +43 °C outdoor and indoor, with indoor humidity below 80 percent. Below -7 °C, the unit is outside its declared envelope, and projects in colder climates need a pre-heat strategy rather than a bigger ventilator. This is a design decision, not an installation detail, and it is better settled at tender stage.
Every model is single-phase 220 to 240 V, 50 Hz, with a 3-core 2.5 mm² supply cable. Current draw runs from 0.64 A on the 200 m³/h model to 5.7 A on the 2,000 m³/h model, so a single dedicated circuit covers the smaller units and the largest ones need their own.
For export projects on other grid standards, the manufacturer supports OEM/ODM voltage customisation from 180 to 440 V at 50 or 60 Hz. That is a factory option, not a field modification, and it needs to be specified on the order.
This is where a ventilator stops being a standalone box and becomes part of a system.
The unit interlocks with Midea VRF indoor units and starts and stops with the air conditioning. When the floor is unoccupied and the VRF is off, the ventilator follows. That single link removes most of the wasted running hours on a typical office floor.
The KJR-27B/E wall controller covers five modes, four fan speeds including a sleep setting, and a timer, with up to 16 units on one controller. The WDC-120G/WK(A) adds CO2 display, filter status, group control, weekly scheduling, VRF interlock and delayed shutdown.
CCM-180A/WS(A) and CCM-270B/WS(A) bring ventilation and VRF under one interface across floors.
GW-MOD(A) delivers Modbus and IMMP-BAC delivers BACnet. Both present the unit as a clean set of points to the building management contractor, rather than as a proprietary device that needs a separate front end.
For a controls contractor, the useful question is not whether the unit supports a protocol but whether the point list is complete at handover. Confirm the gateway model on the order, because it is a factory-fitted option and not something that can be added later without a return visit.
| Model | Airflow | Dimensions L x W x H | Net / gross weight | Spigot | External static pressure | Condensate drain |
|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 1,195 x 801 x 272 mm | 53.6 / 70.6 kg | 144 mm | 100 Pa | Not required |
| HRV-D300(B) | 300 m³/h | 1,195 x 914 x 272 mm | 59 / 77 kg | 144 mm | 90 Pa | Not required |
| HRV-D400(B) | 400 m³/h | 1,276 x 1,204 x 272 mm | 71.5 / 91.5 kg | 198 mm | 100 Pa | Not required |
| HRV-D500(B) | 500 m³/h | 1,311 x 1,106 x 390 mm | 74.4 / 98.6 kg | 244 mm | 90 Pa | Not required |
| HRV-D800(B) | 800 m³/h | 1,311 x 1,286 x 390 mm | 80 / 104 kg | 244 mm | 140 Pa | Not required |
| HRV-D1000(B) | 1,000 m³/h | 1,311 x 1,526 x 390 mm | 90 / 112 kg | 244 mm | 160 Pa | Not required |
| HRV-D1500(B) | 1,500 m³/h | 1,740 x 1,375 x 615 mm | 181.5 / 213 kg | 346 x 326 mm | 180 Pa | PVC required |
| HRV-D2000(B) | 2,000 m³/h | 1,811 x 1,575 x 685 mm | 208.5 / 245 kg | 346 x 326 mm | 200 Pa | PVC required |
All models: single-phase 220 to 240 V, 50 Hz, 3-core 2.5 mm² supply cable. Operating range -7 °C to +43 °C, indoor humidity below 80 percent.
Filters wash or vacuum clean. The core should be vacuumed roughly every two years and must never be washed with water, because the treatment that allows vapour transfer is not designed to survive it. Fans are checked every six months. A differential pressure sensor monitors filter resistance and raises a reminder through the controller before airflow drops, so the schedule is driven by condition rather than by calendar.