Filtration is the part of a ventilation specification that decides how often someone has to climb into the ceiling. The DC Series fits G4 filters as standard on both the supply and exhaust air streams, with F7 on the supply side and M5 on the exhaust side available as options for projects that quote an EU air-quality class. Because both configurations are covered in the engineering manual with published efficiency data, the specification can be modelled rather than guessed.
The filter grade does not depend on which of the eight sizes is selected. A 200 m³/h unit in a villa and a 2,000 m³/h unit on a restaurant floor use the same platform, the same filter positions and the same access panel arrangement. That matters on mixed-use projects, where the ventilation schedule may call for three sizes but only one maintenance procedure.
Filter condition is monitored rather than assumed. A differential pressure sensor watches the loading on the filters and raises a replacement indication on the controller before airflow drops far enough to affect ventilation rates. Filters are washable or vacuum-cleanable, so routine service is a cleaning task rather than a consumable order — and the core behind them needs vacuuming only about every two years, never washing.
| Project requirement | Supply filter | Exhaust filter |
|---|---|---|
| Standard commercial ventilation | G4 | G4 |
| Projects quoting an EU air-quality class | F7 | M5 |
Configurations outside these two should be confirmed with the factory before the specification is issued.
A finer filter adds resistance on the supply side. Because both fans are DC, the unit holds its design airflow without stepping up to the next model size — the trade-off appears in input power, not in airflow.
The headline 82.8% temperature efficiency and 76.0% enthalpy efficiency are measured with the standard G4 filter. Data for the F7 and M5 configuration is published in the engineering manual, so an energy model can use the correct figures instead of a percentage-point assumption.
Finer filters load faster in dusty or high-occupancy environments. The differential pressure sensor is what tells you when, rather than a fixed calendar interval.
The unit carries a differential pressure sensor across the filter section. As the filters load, resistance rises; when it reaches the set point, the controller raises a replacement indication. Because the signal is pressure-based rather than time-based, it responds to the actual environment — a unit beside a construction site and a unit in a clean office do not need the same interval.
Filters are washable or vacuum-cleanable. Wash, dry fully, refit, and the pressure reading returns to its baseline. Where a project prefers replacement over cleaning, the same filter frames accept new media.
| Component | Interval | Method |
|---|---|---|
| Supply and exhaust filters | On controller indication | Wash or vacuum-clean; dry fully before refitting |
| Heat exchange core | Approximately every two years | Vacuum only; never wash with water |
| Fans | Every six months | Inspect for dust build-up and balance |
| Drain (HRV-D1500, D2000 only) | At service visits | Confirm slope and trap are clear |
| Access panel | Every service visit | Confirm the panel is reachable after ceiling closure |
| Space | Typical requirement | Configuration |
|---|---|---|
| Office, retail, restaurant, hotel | Energy-efficient ventilation, low pressure drop | G4 standard |
| School, training centre | Higher supply air quality | F7 supply, M5 exhaust |
| Clinic, healthcare area | Filtration plus balanced supply and exhaust | F7 supply, M5 exhaust |
| Premium office, showroom | Higher supply air quality with BMS monitoring | F7 supply, M5 exhaust |
| Apartment, villa | Standard residential ventilation | G4 standard |
| Model | Airflow | Input power (H/M/L) | Temp. efficiency (H/M/L) | Enthalpy efficiency (H/M/L) | Current | External static pressure | Sound pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; single values measured at high speed. Sound pressure measured 1.5 m below the unit. Efficiency figures are measured with the standard G4 filter; F7 plus M5 data is published in the engineering manual. Operating range -7 °C to +43 °C, indoor humidity below 80%. Only HRV-D1500 and D2000 require a PVC drain.
A: G4 on both the supply and the exhaust air streams, on all eight sizes.
A: Where the project quotes an EU air-quality class — schools, clinics, healthcare areas and premium offices. Offices, retail, restaurants, hotels and apartments normally run the standard G4 configuration.
A: No. The DC fans absorb the additional resistance and hold the design airflow. The trade-off appears in input power, not in delivered air volume.
A: The headline 82.8% temperature efficiency and 76.0% enthalpy efficiency are with the standard G4 filter. F7 and M5 figures are published in the engineering manual for modelling.
A: The differential pressure sensor raises an indication on the controller when resistance reaches the set point. The interval follows the actual environment rather than a fixed calendar.
A: Yes. Both are washable or vacuum-cleanable. Dry them fully before refitting so the pressure reading returns to baseline.
A: No. Vacuum it approximately every two years. Washing damages the treated paper and reduces moisture transfer.
Filtration is the part of a ventilation specification that decides how often someone has to climb into the ceiling. The DC Series fits G4 filters as standard on both the supply and exhaust air streams, with F7 on the supply side and M5 on the exhaust side available as options for projects that quote an EU air-quality class. Because both configurations are covered in the engineering manual with published efficiency data, the specification can be modelled rather than guessed.
The filter grade does not depend on which of the eight sizes is selected. A 200 m³/h unit in a villa and a 2,000 m³/h unit on a restaurant floor use the same platform, the same filter positions and the same access panel arrangement. That matters on mixed-use projects, where the ventilation schedule may call for three sizes but only one maintenance procedure.
Filter condition is monitored rather than assumed. A differential pressure sensor watches the loading on the filters and raises a replacement indication on the controller before airflow drops far enough to affect ventilation rates. Filters are washable or vacuum-cleanable, so routine service is a cleaning task rather than a consumable order — and the core behind them needs vacuuming only about every two years, never washing.
| Project requirement | Supply filter | Exhaust filter |
|---|---|---|
| Standard commercial ventilation | G4 | G4 |
| Projects quoting an EU air-quality class | F7 | M5 |
Configurations outside these two should be confirmed with the factory before the specification is issued.
A finer filter adds resistance on the supply side. Because both fans are DC, the unit holds its design airflow without stepping up to the next model size — the trade-off appears in input power, not in airflow.
The headline 82.8% temperature efficiency and 76.0% enthalpy efficiency are measured with the standard G4 filter. Data for the F7 and M5 configuration is published in the engineering manual, so an energy model can use the correct figures instead of a percentage-point assumption.
Finer filters load faster in dusty or high-occupancy environments. The differential pressure sensor is what tells you when, rather than a fixed calendar interval.
The unit carries a differential pressure sensor across the filter section. As the filters load, resistance rises; when it reaches the set point, the controller raises a replacement indication. Because the signal is pressure-based rather than time-based, it responds to the actual environment — a unit beside a construction site and a unit in a clean office do not need the same interval.
Filters are washable or vacuum-cleanable. Wash, dry fully, refit, and the pressure reading returns to its baseline. Where a project prefers replacement over cleaning, the same filter frames accept new media.
| Component | Interval | Method |
|---|---|---|
| Supply and exhaust filters | On controller indication | Wash or vacuum-clean; dry fully before refitting |
| Heat exchange core | Approximately every two years | Vacuum only; never wash with water |
| Fans | Every six months | Inspect for dust build-up and balance |
| Drain (HRV-D1500, D2000 only) | At service visits | Confirm slope and trap are clear |
| Access panel | Every service visit | Confirm the panel is reachable after ceiling closure |
| Space | Typical requirement | Configuration |
|---|---|---|
| Office, retail, restaurant, hotel | Energy-efficient ventilation, low pressure drop | G4 standard |
| School, training centre | Higher supply air quality | F7 supply, M5 exhaust |
| Clinic, healthcare area | Filtration plus balanced supply and exhaust | F7 supply, M5 exhaust |
| Premium office, showroom | Higher supply air quality with BMS monitoring | F7 supply, M5 exhaust |
| Apartment, villa | Standard residential ventilation | G4 standard |
| Model | Airflow | Input power (H/M/L) | Temp. efficiency (H/M/L) | Enthalpy efficiency (H/M/L) | Current | External static pressure | Sound pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; single values measured at high speed. Sound pressure measured 1.5 m below the unit. Efficiency figures are measured with the standard G4 filter; F7 plus M5 data is published in the engineering manual. Operating range -7 °C to +43 °C, indoor humidity below 80%. Only HRV-D1500 and D2000 require a PVC drain.
A: G4 on both the supply and the exhaust air streams, on all eight sizes.
A: Where the project quotes an EU air-quality class — schools, clinics, healthcare areas and premium offices. Offices, retail, restaurants, hotels and apartments normally run the standard G4 configuration.
A: No. The DC fans absorb the additional resistance and hold the design airflow. The trade-off appears in input power, not in delivered air volume.
A: The headline 82.8% temperature efficiency and 76.0% enthalpy efficiency are with the standard G4 filter. F7 and M5 figures are published in the engineering manual for modelling.
A: The differential pressure sensor raises an indication on the controller when resistance reaches the set point. The interval follows the actual environment rather than a fixed calendar.
A: Yes. Both are washable or vacuum-cleanable. Dry them fully before refitting so the pressure reading returns to baseline.
A: No. Vacuum it approximately every two years. Washing damages the treated paper and reduces moisture transfer.