The DC series heat recovery ventilator offers five operating modes, one of which is bypass. In bypass mode, outdoor air is routed around the heat exchange core rather than through it, so supply air reaches the diffuser at close to outdoor temperature. That behaviour is undesirable in January and exactly right in April.
The real value lies in the shoulder seasons and in night purge. When outdoor air is cooler than the space, admitting it without heat recovery removes sensible load without running a compressor. The same unit that recovers up to 82.8% of heat in winter becomes a free cooling device in spring, autumn and at night — with no additional hardware and no additional refrigerant circuit.
The limits matter as much as the benefit. Bypass delivers sensible cooling only. It does not dehumidify, and in a hot humid climate it can raise the latent load and condensation risk instead of lowering it. This page sets out where bypass pays, where it does not, and how to commission the automatic changeover so it performs as the design intended.
| Mode | Air Path | When It Is Used |
|---|---|---|
| Auto | Recovery or bypass, selected by comparison | Normal operation where the building runs year-round |
| Heat recovery | Both streams through the core | Heating season, and cooling season where outdoor air is hotter |
| Bypass | Outdoor air routed around the core | Shoulder seasons, night purge, high internal gains |
| Exhaust only | Exhaust fan running, supply stopped | Odour or pollutant extraction without introducing outdoor air |
| Supply only | Supply fan running, exhaust stopped | Pressurisation, or where extraction is handled separately |
Auto mode compares outdoor temperature with indoor temperature and chooses between recovery and bypass. Where outdoor air is cooler than the space, bypass is the better choice because the incoming air provides sensible cooling. Where outdoor air is hotter, recovery is better because it reduces the load the cooling system must remove.
The comparison is a temperature comparison, not an enthalpy comparison. That distinction is the single most important thing to understand about this function: on a mild but very humid day, outdoor air can be cooler than the space and still carry more total energy because of the moisture it brings in. Auto mode will select bypass in that condition, because the temperature says so.
Sensible cooling from ventilation is straightforward to estimate. At 1,000 m³/h, each kelvin of temperature difference between outdoor air and room air carries about 0.335 kW.
| Outdoor-to-room difference | Sensible cooling at 1,000 m³/h | Sensible cooling at 2,000 m³/h |
|---|---|---|
| 3 K | 1.0 kW | 2.0 kW |
| 5 K | 1.7 kW | 3.3 kW |
| 8 K | 2.7 kW | 5.4 kW |
Those figures are cooling delivered with the compressor off. In a space with high internal gains — a classroom, a restaurant floor, a gym, an open-plan office — a 5 K difference at 2,000 m³/h removes 3.3 kW of load for the cost of the fan, which draws 500 W at medium speed on the 2,000 m³/h size. That ratio is the whole argument for bypass.
The reverse is also true. In heating season the same damper closes and the core recovers up to 82.8% of the heat, so the unit is not giving away the winter benefit to obtain the spring one.
Bypass moves air. It does not remove moisture. In a hot humid climate, outdoor air at 28 °C and 80% RH carries a large latent load, and admitting it without recovery adds that load to the space. The room may even feel worse at the same dry-bulb temperature, because the moisture reduces evaporative cooling from skin.
Three practical consequences follow. First, in humid climates, bypass should be enabled on a schedule or a condition the operator controls, not left permanently in Auto. Second, where a project has a dedicated dehumidification requirement, the ventilation strategy should be settled before the unit is selected rather than after. Third, ducts carrying bypassed outdoor air through unconditioned or cooled space must be insulated, because a cold duct surface in a humid ceiling void condenses.
In a temperate or dry climate none of this changes the case for bypass. The distinction is climate, not product.
Night purge uses the same damper for a different purpose: running the unit at night with bypass open flushes the warm air that has accumulated in the structure during the day, so the cooling system starts the morning from a lower base. The WDC-120G/WK(A) controller supports weekly timing, so purge can be scheduled without a BMS on small and medium projects.
Two conditions decide whether it works. The outdoor temperature at night has to be meaningfully below the indoor temperature, otherwise the fan runs for nothing. And the building has to be able to accept the air path — an open-plan floor with a return path works; a series of closed offices does not.
| Model | Airflow | Input power (H/M/L) | Temp. efficiency (H/M/L) | Enthalpy efficiency (H/M/L) | Current | External static pressure | Sound pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; airflow and other single values are measured at high speed. Efficiency figures apply to heat recovery mode and are measured with the standard G4 filter. The specification table is identical across all versions of this product page.
Q1. What does bypass actually do?
It routes outdoor air around the heat exchange core, so the air reaches the space at close to outdoor temperature. It is used when outdoor air is cooler than the space and free cooling is wanted.
Q2. Is the bypass damper an optional extra?
No. It is part of the standard unit across all eight sizes.
Q3. How does Auto mode decide?
By comparing outdoor and indoor temperature. Note that this is a temperature comparison, not an enthalpy comparison, which matters in humid climates.
Q4. Can bypass replace air conditioning?
No. It delivers sensible cooling only, and only when outdoor air is cooler than the space. It reduces load and compressor runtime; it does not control temperature on its own.
Q5. Why is bypass a problem in humid climates?
Because it admits moisture without recovery. The room can feel worse at the same temperature, and cold duct surfaces in a humid void will condense. Use a schedule or operator control rather than permanent Auto in those climates.
Q6. What is night purge?
Running the unit at night with bypass open to flush warm air from the structure, so the cooling system starts the next day from a lower base. It needs a genuine night-time temperature difference and an air path through the building.
Q7. Can bypass run without a BMS?
Yes. Mode selection is available from the wired controller, and the WDC-120G/WK(A) controller adds weekly timing for night purge.
The DC series heat recovery ventilator offers five operating modes, one of which is bypass. In bypass mode, outdoor air is routed around the heat exchange core rather than through it, so supply air reaches the diffuser at close to outdoor temperature. That behaviour is undesirable in January and exactly right in April.
The real value lies in the shoulder seasons and in night purge. When outdoor air is cooler than the space, admitting it without heat recovery removes sensible load without running a compressor. The same unit that recovers up to 82.8% of heat in winter becomes a free cooling device in spring, autumn and at night — with no additional hardware and no additional refrigerant circuit.
The limits matter as much as the benefit. Bypass delivers sensible cooling only. It does not dehumidify, and in a hot humid climate it can raise the latent load and condensation risk instead of lowering it. This page sets out where bypass pays, where it does not, and how to commission the automatic changeover so it performs as the design intended.
| Mode | Air Path | When It Is Used |
|---|---|---|
| Auto | Recovery or bypass, selected by comparison | Normal operation where the building runs year-round |
| Heat recovery | Both streams through the core | Heating season, and cooling season where outdoor air is hotter |
| Bypass | Outdoor air routed around the core | Shoulder seasons, night purge, high internal gains |
| Exhaust only | Exhaust fan running, supply stopped | Odour or pollutant extraction without introducing outdoor air |
| Supply only | Supply fan running, exhaust stopped | Pressurisation, or where extraction is handled separately |
Auto mode compares outdoor temperature with indoor temperature and chooses between recovery and bypass. Where outdoor air is cooler than the space, bypass is the better choice because the incoming air provides sensible cooling. Where outdoor air is hotter, recovery is better because it reduces the load the cooling system must remove.
The comparison is a temperature comparison, not an enthalpy comparison. That distinction is the single most important thing to understand about this function: on a mild but very humid day, outdoor air can be cooler than the space and still carry more total energy because of the moisture it brings in. Auto mode will select bypass in that condition, because the temperature says so.
Sensible cooling from ventilation is straightforward to estimate. At 1,000 m³/h, each kelvin of temperature difference between outdoor air and room air carries about 0.335 kW.
| Outdoor-to-room difference | Sensible cooling at 1,000 m³/h | Sensible cooling at 2,000 m³/h |
|---|---|---|
| 3 K | 1.0 kW | 2.0 kW |
| 5 K | 1.7 kW | 3.3 kW |
| 8 K | 2.7 kW | 5.4 kW |
Those figures are cooling delivered with the compressor off. In a space with high internal gains — a classroom, a restaurant floor, a gym, an open-plan office — a 5 K difference at 2,000 m³/h removes 3.3 kW of load for the cost of the fan, which draws 500 W at medium speed on the 2,000 m³/h size. That ratio is the whole argument for bypass.
The reverse is also true. In heating season the same damper closes and the core recovers up to 82.8% of the heat, so the unit is not giving away the winter benefit to obtain the spring one.
Bypass moves air. It does not remove moisture. In a hot humid climate, outdoor air at 28 °C and 80% RH carries a large latent load, and admitting it without recovery adds that load to the space. The room may even feel worse at the same dry-bulb temperature, because the moisture reduces evaporative cooling from skin.
Three practical consequences follow. First, in humid climates, bypass should be enabled on a schedule or a condition the operator controls, not left permanently in Auto. Second, where a project has a dedicated dehumidification requirement, the ventilation strategy should be settled before the unit is selected rather than after. Third, ducts carrying bypassed outdoor air through unconditioned or cooled space must be insulated, because a cold duct surface in a humid ceiling void condenses.
In a temperate or dry climate none of this changes the case for bypass. The distinction is climate, not product.
Night purge uses the same damper for a different purpose: running the unit at night with bypass open flushes the warm air that has accumulated in the structure during the day, so the cooling system starts the morning from a lower base. The WDC-120G/WK(A) controller supports weekly timing, so purge can be scheduled without a BMS on small and medium projects.
Two conditions decide whether it works. The outdoor temperature at night has to be meaningfully below the indoor temperature, otherwise the fan runs for nothing. And the building has to be able to accept the air path — an open-plan floor with a return path works; a series of closed offices does not.
| Model | Airflow | Input power (H/M/L) | Temp. efficiency (H/M/L) | Enthalpy efficiency (H/M/L) | Current | External static pressure | Sound pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; airflow and other single values are measured at high speed. Efficiency figures apply to heat recovery mode and are measured with the standard G4 filter. The specification table is identical across all versions of this product page.
Q1. What does bypass actually do?
It routes outdoor air around the heat exchange core, so the air reaches the space at close to outdoor temperature. It is used when outdoor air is cooler than the space and free cooling is wanted.
Q2. Is the bypass damper an optional extra?
No. It is part of the standard unit across all eight sizes.
Q3. How does Auto mode decide?
By comparing outdoor and indoor temperature. Note that this is a temperature comparison, not an enthalpy comparison, which matters in humid climates.
Q4. Can bypass replace air conditioning?
No. It delivers sensible cooling only, and only when outdoor air is cooler than the space. It reduces load and compressor runtime; it does not control temperature on its own.
Q5. Why is bypass a problem in humid climates?
Because it admits moisture without recovery. The room can feel worse at the same temperature, and cold duct surfaces in a humid void will condense. Use a schedule or operator control rather than permanent Auto in those climates.
Q6. What is night purge?
Running the unit at night with bypass open to flush warm air from the structure, so the cooling system starts the next day from a lower base. It needs a genuine night-time temperature difference and an air path through the building.
Q7. Can bypass run without a BMS?
Yes. Mode selection is available from the wired controller, and the WDC-120G/WK(A) controller adds weekly timing for night purge.