The DC series heat recovery ventilator uses full DC motors on both the supply and exhaust air streams. Low-speed sound pressure starts at 24.5 dB(A) measured 1.5 m below the unit, and the full range stays between 24.5 and 53 dB(A) across three fan speeds. Eight sizes cover 200 to 2,000 m³/h, so the same acoustic platform serves a hotel guest room and an open-plan office floor.
Most ventilation noise complaints do not come from a unit running at design duty. They come from a unit sized too small and forced to run at high speed permanently, or from a unit mounted without any thought to where the sound goes. This page publishes the acoustic data for every size and every speed, plus the installation measures that decide whether the published figure survives contact with the ceiling void.
Sound pressure and sound power are both listed. Sound pressure is what a person hears at a stated distance and depends on the room; sound power is what the unit emits and is independent of the room. Acoustic consultants specify against sound power because it can be compared across products and rooms. Both are needed to answer a tender question without guessing.
Sound pressure (dB(A)) is measured in a room at a stated distance. The figures on this page are taken at 1.5 m below the unit. The number changes with room absorption, ceiling construction and nearby surfaces, which is why two installations of the same model can measure differently.
Sound power (dB) describes the unit itself and does not change with the room. It is the figure to hand to an acoustic consultant or to compare against a project specification. Both are published below so the same unit can be checked at either level.
| Model | Sound Pressure H/M/L dB(A) at 1.5 m | Sound Power dB |
|---|---|---|
| HRV-D200(B) | 33 / 29.5 / 25.5 | 45 |
| HRV-D300(B) | 36.5 / 33.5 / 30 | 48 |
| HRV-D400(B) | 36.5 / 32 / 28 | 48 |
| HRV-D500(B) | 36 / 30.5 / 24.5 | 50 |
| HRV-D800(B) | 42 / 39 / 34 | 55 |
| HRV-D1000(B) | 44 / 39 / 33.5 | 54 |
| HRV-D1500(B) | 51.5 / 46.5 / 41.5 | 69 |
| HRV-D2000(B) | 53 / 48.5 / 42.5 | 70 |
Three sources matter, and only one of them is the fan.
Dominated by rotational speed. Halving fan speed cuts sound power far more than it cuts airflow, which is why low speed is disproportionately quiet. DC motors hold a stable low speed without the hum that AC motors develop when throttled.
Generated by velocity through the casing, the filter and the duct. A unit with a clean filter and a generous duct size is quieter than the same unit with a loaded filter and an undersized duct. This is the source most often created on site rather than in the factory.
Caused by vibration transmitted into the ceiling structure. Rigid mounting brackets and short, straight duct connections transmit more; flexible connectors and anti-vibration mounts remove most of it.
Heat recovery efficiency rises as airflow drops, on this series and on most paper-core units. At 1,000 m³/h the temperature efficiency is 82.8% at high speed, 84.0% at medium and 87.4% at low. Running at low speed therefore improves both the acoustic result and the recovery result, and reduces fan power at the same time.
The constraint is the ventilation requirement, not the unit. Once the design airflow is fixed, choosing a size that reaches that airflow at low or medium speed gives a quieter installation than choosing a size that reaches it at high speed. A 1,000 m³/h duty served by a 1,500 m³/h unit at low speed is a different acoustic proposition from the same duty served by a 1,000 m³/h unit at high speed.
| Space | Approach | Recommended Size | Low Speed dB(A) |
|---|---|---|---|
| Hotel guest room, apartment bedroom | Low speed as the normal operating point | D200, D300 | 25.5 / 30 |
| Meeting room, small office | Low or medium speed with CO2 control | D300, D400, D500 | 30 / 28 / 24.5 |
| Classroom, training room | Medium speed, duct silencer where the unit sits above the room | D800, D1000 | 34 / 33.5 |
| Open-plan office | Low speed on a larger size, plus duct silencers | D1000, D1500 | 33.5 / 41.5 |
| Restaurant, gym | High speed is unavoidable; acoustic treatment moves to the duct | D1500, D2000 | 41.5 / 42.5 |
Where the unit is installed directly above an occupied space, a duct silencer on the supply and return branches is normally the single most effective measure. Silencers add static pressure, so the fan duty must be checked against the added resistance before the size is fixed.
| Model | Airflow | Input Power (H/M/L) | Temp. Efficiency (H/M/L) | Enthalpy Efficiency (H/M/L) | Current | External Static Pressure | Sound Pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; airflow and other single values are measured at high speed. Sound pressure measured 1.5 m below the unit. Efficiency figures are measured with the standard G4 filter. The specification table is identical across all versions of this product page.
Q1. What is the difference between sound pressure and sound power?
Sound pressure is what you measure in a room at a stated distance and depends on the room. Sound power describes the source and is independent of the room. Use sound power for acoustic modelling and specification comparison, sound pressure for what a person will actually hear.
Q2. At what distance is the sound pressure measured?
1.5 m below the unit, per the engineering manual. Any figure quoted at a different distance is not directly comparable.
Q3. Which size is the quietest?
The 500 m³/h size reaches 24.5 dB(A) at low speed, the lowest figure in the range. In practice the quietest installation is usually a larger size running at low speed for a given airflow, because the same duty is met with a lower fan speed.
Q4. Does higher airflow always mean more noise?
No. Noise follows fan speed more closely than it follows nominal airflow. A 1,500 m³/h unit delivering 1,000 m³/h at low speed is generally quieter than a 1,000 m³/h unit delivering the same airflow at high speed.
Q5. Do I need duct silencers?
Where the unit sits directly above an occupied space, yes in most cases. A silencer on the supply and return branches is usually the most effective single measure. Silencers add static pressure, so check the fan duty against the added resistance.
Q6. Can the unit run at low speed continuously?
Yes. Low speed is a designed duty point on DC motors, not a throttled condition. Efficiency is also higher at low speed, so continuous low-speed operation is the better operating mode where the ventilation requirement allows it.
Q7. Does the filter affect noise?
A loaded filter raises system resistance and the fan compensates by increasing speed, which raises noise. The optional F7 supply and M5 exhaust configuration also adds resistance compared with the G4 standard. Keep filters clean and size the fan duty for the filter configuration actually specified.
The DC series heat recovery ventilator uses full DC motors on both the supply and exhaust air streams. Low-speed sound pressure starts at 24.5 dB(A) measured 1.5 m below the unit, and the full range stays between 24.5 and 53 dB(A) across three fan speeds. Eight sizes cover 200 to 2,000 m³/h, so the same acoustic platform serves a hotel guest room and an open-plan office floor.
Most ventilation noise complaints do not come from a unit running at design duty. They come from a unit sized too small and forced to run at high speed permanently, or from a unit mounted without any thought to where the sound goes. This page publishes the acoustic data for every size and every speed, plus the installation measures that decide whether the published figure survives contact with the ceiling void.
Sound pressure and sound power are both listed. Sound pressure is what a person hears at a stated distance and depends on the room; sound power is what the unit emits and is independent of the room. Acoustic consultants specify against sound power because it can be compared across products and rooms. Both are needed to answer a tender question without guessing.
Sound pressure (dB(A)) is measured in a room at a stated distance. The figures on this page are taken at 1.5 m below the unit. The number changes with room absorption, ceiling construction and nearby surfaces, which is why two installations of the same model can measure differently.
Sound power (dB) describes the unit itself and does not change with the room. It is the figure to hand to an acoustic consultant or to compare against a project specification. Both are published below so the same unit can be checked at either level.
| Model | Sound Pressure H/M/L dB(A) at 1.5 m | Sound Power dB |
|---|---|---|
| HRV-D200(B) | 33 / 29.5 / 25.5 | 45 |
| HRV-D300(B) | 36.5 / 33.5 / 30 | 48 |
| HRV-D400(B) | 36.5 / 32 / 28 | 48 |
| HRV-D500(B) | 36 / 30.5 / 24.5 | 50 |
| HRV-D800(B) | 42 / 39 / 34 | 55 |
| HRV-D1000(B) | 44 / 39 / 33.5 | 54 |
| HRV-D1500(B) | 51.5 / 46.5 / 41.5 | 69 |
| HRV-D2000(B) | 53 / 48.5 / 42.5 | 70 |
Three sources matter, and only one of them is the fan.
Dominated by rotational speed. Halving fan speed cuts sound power far more than it cuts airflow, which is why low speed is disproportionately quiet. DC motors hold a stable low speed without the hum that AC motors develop when throttled.
Generated by velocity through the casing, the filter and the duct. A unit with a clean filter and a generous duct size is quieter than the same unit with a loaded filter and an undersized duct. This is the source most often created on site rather than in the factory.
Caused by vibration transmitted into the ceiling structure. Rigid mounting brackets and short, straight duct connections transmit more; flexible connectors and anti-vibration mounts remove most of it.
Heat recovery efficiency rises as airflow drops, on this series and on most paper-core units. At 1,000 m³/h the temperature efficiency is 82.8% at high speed, 84.0% at medium and 87.4% at low. Running at low speed therefore improves both the acoustic result and the recovery result, and reduces fan power at the same time.
The constraint is the ventilation requirement, not the unit. Once the design airflow is fixed, choosing a size that reaches that airflow at low or medium speed gives a quieter installation than choosing a size that reaches it at high speed. A 1,000 m³/h duty served by a 1,500 m³/h unit at low speed is a different acoustic proposition from the same duty served by a 1,000 m³/h unit at high speed.
| Space | Approach | Recommended Size | Low Speed dB(A) |
|---|---|---|---|
| Hotel guest room, apartment bedroom | Low speed as the normal operating point | D200, D300 | 25.5 / 30 |
| Meeting room, small office | Low or medium speed with CO2 control | D300, D400, D500 | 30 / 28 / 24.5 |
| Classroom, training room | Medium speed, duct silencer where the unit sits above the room | D800, D1000 | 34 / 33.5 |
| Open-plan office | Low speed on a larger size, plus duct silencers | D1000, D1500 | 33.5 / 41.5 |
| Restaurant, gym | High speed is unavoidable; acoustic treatment moves to the duct | D1500, D2000 | 41.5 / 42.5 |
Where the unit is installed directly above an occupied space, a duct silencer on the supply and return branches is normally the single most effective measure. Silencers add static pressure, so the fan duty must be checked against the added resistance before the size is fixed.
| Model | Airflow | Input Power (H/M/L) | Temp. Efficiency (H/M/L) | Enthalpy Efficiency (H/M/L) | Current | External Static Pressure | Sound Pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; airflow and other single values are measured at high speed. Sound pressure measured 1.5 m below the unit. Efficiency figures are measured with the standard G4 filter. The specification table is identical across all versions of this product page.
Q1. What is the difference between sound pressure and sound power?
Sound pressure is what you measure in a room at a stated distance and depends on the room. Sound power describes the source and is independent of the room. Use sound power for acoustic modelling and specification comparison, sound pressure for what a person will actually hear.
Q2. At what distance is the sound pressure measured?
1.5 m below the unit, per the engineering manual. Any figure quoted at a different distance is not directly comparable.
Q3. Which size is the quietest?
The 500 m³/h size reaches 24.5 dB(A) at low speed, the lowest figure in the range. In practice the quietest installation is usually a larger size running at low speed for a given airflow, because the same duty is met with a lower fan speed.
Q4. Does higher airflow always mean more noise?
No. Noise follows fan speed more closely than it follows nominal airflow. A 1,500 m³/h unit delivering 1,000 m³/h at low speed is generally quieter than a 1,000 m³/h unit delivering the same airflow at high speed.
Q5. Do I need duct silencers?
Where the unit sits directly above an occupied space, yes in most cases. A silencer on the supply and return branches is usually the most effective single measure. Silencers add static pressure, so check the fan duty against the added resistance.
Q6. Can the unit run at low speed continuously?
Yes. Low speed is a designed duty point on DC motors, not a throttled condition. Efficiency is also higher at low speed, so continuous low-speed operation is the better operating mode where the ventilation requirement allows it.
Q7. Does the filter affect noise?
A loaded filter raises system resistance and the fan compensates by increasing speed, which raises noise. The optional F7 supply and M5 exhaust configuration also adds resistance compared with the G4 standard. Keep filters clean and size the fan duty for the filter configuration actually specified.