A fixed-speed heat recovery ventilator is a constant load, not a controlled one. The DC Series is engineered so ventilation follows occupancy instead of design peak: an optional CO2 sensor steps fan speed across four thresholds, the bypass damper switches to free cooling automatically, and the PQE port synchronises the unit with Midea VRF indoor units so air handling and ventilation start and stop together.
Control is layered by project size. A single KJR-27B/E wired controller covers five modes, four fan speeds including a sleep setting, and timer on/off, and can manage up to 16 units from one position. The WDC-120G/WK(A) controller adds CO2 concentration display, filter indication, group control, weekly timer, VRF interlock, delayed shutdown and parameter query — enough for a whole floor without a BMS. Above that, CCM-180A/WS(A) and CCM-270B/WS(A) centralised controllers bring HRV and VRF onto one panel for multi-floor management.
Handover to building management is a specification decision, not a retrofit. GW-MOD(A) delivers Modbus RTU and IMMP-BAC delivers BACnet, so ventilation points land in the BMS alongside the rest of the plant. Because the unit is DC-driven with a differential pressure sensor on the filters, the BMS also sees what maintenance needs to know: when a filter is loading up, before airflow drops.
| Mode | Behaviour | Typical Use |
|---|---|---|
| Auto | Compares indoor and outdoor temperature, selects heat recovery or bypass, both fans at low speed | Everyday operation |
| Heat Recovery | Both air streams pass through the core; supply pre-cooled in summer, pre-warmed in winter | Heating and cooling seasons |
| Bypass | Fresh air routes around the core for free cooling; supply and exhaust at matched speed | Shoulder seasons, night purge |
| Exhaust | Extract only | Kitchens, toilets, smoking areas |
| Supply | Fresh air only | Positive-pressure requirements |
| Device | Function | Capacity |
|---|---|---|
| KJR-27B/E wired controller | Five modes, four fan speeds including sleep, timer on/off | Up to 16 units per controller |
| WDC-120G/WK(A) wired controller | CO2 display, filter indication, group control, weekly timer, VRF interlock, delayed shutdown, parameter query | Group and floor level |
| CCM-180A/WS(A) centralised controller | HRV and VRF managed together by floor and zone | Multi-floor projects |
| CCM-270B/WS(A) centralised controller | Centralised monitoring and control of HRV and VRF | Multi-floor projects |
| GW-MOD(A) gateway | Modbus RTU interface to the BMS | Per project |
| IMMP-BAC gateway | BACnet interface to the BMS | Per project |
| PQE port | Interlock with Midea VRF indoor units | Per unit |
| CO2 sensor box (optional) | Demand-controlled ventilation | Per unit |
The optional CO2 sensor converts the unit from constant volume to demand-controlled ventilation. Fan speed steps automatically as concentration crosses each threshold, so a meeting room used eight hours a day does not run at design airflow for the other sixteen.
| CO2 Concentration | Fan Response |
|---|---|
| Below 450 ppm | Stop |
| 550 ppm | Low speed |
| 800 ppm | Medium speed |
| 1,000 ppm | High speed |
Thresholds are set at commissioning against the project's ventilation strategy. Where a space has a known peak occupancy, the 1,000 ppm step should correspond to design airflow so the unit can still meet the calculated requirement at full occupancy.
The PQE port links the HRV to Midea VRF indoor units, so ventilation follows the air conditioning rather than a separate time schedule. In practice this removes the most common operational failure on commercial floors: air conditioning switched off while the ventilator still runs, or the reverse. One KJR-27B/E controller can manage up to 16 units, which covers a typical floor from a single position without a BMS.
Where the project spans multiple floors or zones, CCM-180A/WS(A) and CCM-270B/WS(A) centralised controllers put HRV and VRF on the same panel, giving facility staff one interface instead of two systems.
| Model | Airflow | Input Power (H/M/L) | Temp. Efficiency (H/M/L) | Enthalpy Efficiency (H/M/L) | Current | External Static Pressure | Sound Pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
The CO2 sensor box is an option and works with the WDC-120G/WK(A) controller, which displays concentration and manages the four thresholds. The KJR-27B/E controller covers the five operating modes and fan speeds.
Yes. A single KJR-27B/E controller manages up to 16 units, and the WDC-120G/WK(A) adds group control for floor-level management.
The PQE port connects the HRV to Midea VRF indoor units, so the ventilator starts and stops with the air conditioning group it belongs to. There is no separate time schedule to keep in step.
The gateway maps the unit's control and status points into Modbus registers or BACnet objects. The point list is issued at order stage so the BMS contractor can schedule it before delivery.
Yes. All functions are available from the wired controller. If the BMS or gateway is unavailable, ventilation continues on local control.
They are set at commissioning against the ventilation strategy, and can be revised on site when occupancy patterns change. Record any change in the O&M manual.
A low-voltage control cable from the controller position to the unit, in addition to the single-phase 220-240 V power supply. Route control cable separately from power cable.
A fixed-speed heat recovery ventilator is a constant load, not a controlled one. The DC Series is engineered so ventilation follows occupancy instead of design peak: an optional CO2 sensor steps fan speed across four thresholds, the bypass damper switches to free cooling automatically, and the PQE port synchronises the unit with Midea VRF indoor units so air handling and ventilation start and stop together.
Control is layered by project size. A single KJR-27B/E wired controller covers five modes, four fan speeds including a sleep setting, and timer on/off, and can manage up to 16 units from one position. The WDC-120G/WK(A) controller adds CO2 concentration display, filter indication, group control, weekly timer, VRF interlock, delayed shutdown and parameter query — enough for a whole floor without a BMS. Above that, CCM-180A/WS(A) and CCM-270B/WS(A) centralised controllers bring HRV and VRF onto one panel for multi-floor management.
Handover to building management is a specification decision, not a retrofit. GW-MOD(A) delivers Modbus RTU and IMMP-BAC delivers BACnet, so ventilation points land in the BMS alongside the rest of the plant. Because the unit is DC-driven with a differential pressure sensor on the filters, the BMS also sees what maintenance needs to know: when a filter is loading up, before airflow drops.
| Mode | Behaviour | Typical Use |
|---|---|---|
| Auto | Compares indoor and outdoor temperature, selects heat recovery or bypass, both fans at low speed | Everyday operation |
| Heat Recovery | Both air streams pass through the core; supply pre-cooled in summer, pre-warmed in winter | Heating and cooling seasons |
| Bypass | Fresh air routes around the core for free cooling; supply and exhaust at matched speed | Shoulder seasons, night purge |
| Exhaust | Extract only | Kitchens, toilets, smoking areas |
| Supply | Fresh air only | Positive-pressure requirements |
| Device | Function | Capacity |
|---|---|---|
| KJR-27B/E wired controller | Five modes, four fan speeds including sleep, timer on/off | Up to 16 units per controller |
| WDC-120G/WK(A) wired controller | CO2 display, filter indication, group control, weekly timer, VRF interlock, delayed shutdown, parameter query | Group and floor level |
| CCM-180A/WS(A) centralised controller | HRV and VRF managed together by floor and zone | Multi-floor projects |
| CCM-270B/WS(A) centralised controller | Centralised monitoring and control of HRV and VRF | Multi-floor projects |
| GW-MOD(A) gateway | Modbus RTU interface to the BMS | Per project |
| IMMP-BAC gateway | BACnet interface to the BMS | Per project |
| PQE port | Interlock with Midea VRF indoor units | Per unit |
| CO2 sensor box (optional) | Demand-controlled ventilation | Per unit |
The optional CO2 sensor converts the unit from constant volume to demand-controlled ventilation. Fan speed steps automatically as concentration crosses each threshold, so a meeting room used eight hours a day does not run at design airflow for the other sixteen.
| CO2 Concentration | Fan Response |
|---|---|
| Below 450 ppm | Stop |
| 550 ppm | Low speed |
| 800 ppm | Medium speed |
| 1,000 ppm | High speed |
Thresholds are set at commissioning against the project's ventilation strategy. Where a space has a known peak occupancy, the 1,000 ppm step should correspond to design airflow so the unit can still meet the calculated requirement at full occupancy.
The PQE port links the HRV to Midea VRF indoor units, so ventilation follows the air conditioning rather than a separate time schedule. In practice this removes the most common operational failure on commercial floors: air conditioning switched off while the ventilator still runs, or the reverse. One KJR-27B/E controller can manage up to 16 units, which covers a typical floor from a single position without a BMS.
Where the project spans multiple floors or zones, CCM-180A/WS(A) and CCM-270B/WS(A) centralised controllers put HRV and VRF on the same panel, giving facility staff one interface instead of two systems.
| Model | Airflow | Input Power (H/M/L) | Temp. Efficiency (H/M/L) | Enthalpy Efficiency (H/M/L) | Current | External Static Pressure | Sound Pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
The CO2 sensor box is an option and works with the WDC-120G/WK(A) controller, which displays concentration and manages the four thresholds. The KJR-27B/E controller covers the five operating modes and fan speeds.
Yes. A single KJR-27B/E controller manages up to 16 units, and the WDC-120G/WK(A) adds group control for floor-level management.
The PQE port connects the HRV to Midea VRF indoor units, so the ventilator starts and stops with the air conditioning group it belongs to. There is no separate time schedule to keep in step.
The gateway maps the unit's control and status points into Modbus registers or BACnet objects. The point list is issued at order stage so the BMS contractor can schedule it before delivery.
Yes. All functions are available from the wired controller. If the BMS or gateway is unavailable, ventilation continues on local control.
They are set at commissioning against the ventilation strategy, and can be revised on site when occupancy patterns change. Record any change in the O&M manual.
A low-voltage control cable from the controller position to the unit, in addition to the single-phase 220-240 V power supply. Route control cable separately from power cable.