The two large sizes in the DC series deliver 1,500 and 2,000 m³/h against 180 and 200 Pa of external static pressure, through 346 × 326 mm rectangular spigots. Both use full DC motors on the supply and exhaust side, and both require a PVC condensate drain because of the air volume they move.
These sizes exist for spaces where ventilation load is set by occupancy rather than by floor area: restaurant floors, gyms, assembly halls, open-plan office floors and retail. In those spaces the duct run is long, the fittings are many, and the available static pressure decides whether the design airflow actually arrives at the diffuser. A unit rated at 2,000 m³/h with no pressure left is a 1,400 m³/h unit in practice.
Heat recovery at this scale is not a rounding error. At 2,000 m³/h with a 25 K temperature difference, the untreated ventilation load is around 16.8 kW; at the 83.4% low-speed efficiency of the 2,000 m³/h size, the residual load falls to about 2.8 kW. That difference is what separates a space that meets its ventilation requirement from a space that meets it and still keeps the plant size down.
| Item | HRV-D1500(B) | HRV-D2000(B) |
|---|---|---|
| Airflow (m³/h) | 1,500 | 2,000 |
| Input power H/M/L (W) | 680 / 320 / 200 | 950 / 500 / 230 |
| External static pressure (Pa) | 180 | 200 |
| Temperature efficiency H/M/L (%) | 75.5 / 78.6 / 80.2 | 77.2 / 79.5 / 83.4 |
| Enthalpy efficiency H/M/L (%) | 69.4 / 71.2 / 74.8 | 74.7 / 77.0 / 80.6 |
| Current (A) | 3.8 | 5.7 |
| Sound pressure H/M/L dB(A) at 1.5 m | 51.5 / 46.5 / 41.5 | 53 / 48.5 / 42.5 |
| Sound power (dB) | 69 | 70 |
| Dimensions L × W × H (mm) | 1740 × 1375 × 615 | 1811 × 1575 × 685 |
| Net / gross weight (kg) | 181.5 / 213 | 208.5 / 245 |
| Duct spigot | 346 × 326 mm | 346 × 326 mm |
A 2,000 m³/h unit is only as good as the duct system attached to it. The 346 × 326 mm spigot carries roughly 0.48 m² of face area, so the trunk velocity at 2,000 m³/h sits near 1.2 m/s at the spigot itself — comfortable, and the reason the rectangular connection is worth using rather than reducing to round immediately.
The 200 Pa figure is the budget for everything downstream: duct, elbows, tees, silencers, fire dampers, grilles and the diffusers themselves. A restaurant floor with a long run and several branch take-offs will consume most of it. Two practical rules follow. First, calculate the pressure loss before fixing the model, not after. Second, if silencers are added for acoustic reasons, they consume static pressure too and the size may need to move up.
Where the calculated loss exceeds the available pressure, the answer is usually duct sizing rather than a bigger unit. Increasing the trunk from 346 × 326 to the next size up drops velocity and loss faster than moving to a larger model increases available pressure.
Both large sizes require a PVC condensate drain. That is a design requirement, not an option: at these air volumes the moisture removed from the exhaust stream has to go somewhere, and the unit is normally installed in a plant room or a service bulkhead where a drain route exists.
The casing is 615 mm on the 1,500 m³/h size and 685 mm on the 2,000 m³/h size, with net weights of 181.5 and 208.5 kg. These are plant room or bulkhead units, not ceiling void units. Two people cannot lift them, the structure needs to be checked, and access for filter service has to be designed in from the start.
Efficiency on this series falls as airflow rises, which is why the large sizes show lower figures than the residential ones. At 1,500 m³/h the temperature efficiency is 75.5% at high speed, 78.6% at medium and 80.2% at low. At 2,000 m³/h it is 77.2%, 79.5% and 83.4%.
The practical consequence is that the last 25% of airflow costs disproportionately. Where a space can be served at 1,500 m³/h instead of 2,000 m³/h, both the efficiency and the fan power improve. Where 2,000 m³/h is genuinely required, the low-speed figure of 83.4% is the one to use in the energy calculation, provided the design allows low-speed operation as the normal condition.
| Model | Airflow | Input power (H/M/L) | Temp. efficiency (H/M/L) | Enthalpy efficiency (H/M/L) | Current | External static pressure | Sound pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; airflow and other single values are measured at high speed. Efficiency figures are measured with the standard G4 filter. The specification table is identical across all versions of this product page.
A: 2,000 m³/h on the HRV-D2000(B), rated against 200 Pa external static pressure.
A: It depends on the run. 200 Pa has to cover duct, elbows, silencers, dampers and grilles. Calculate the loss first; where it exceeds the available pressure, increase the duct size before moving to a larger model.
A: Yes. Both the 1,500 and 2,000 m³/h sizes require a PVC condensate drain. The 200 to 1,000 m³/h sizes do not.
A: Not normally. Casing depth is 615 mm and 685 mm with net weights of 181.5 and 208.5 kg. These are plant room or service bulkhead units, and the structure must be checked.
A: 346 × 326 mm rectangular spigots on both sizes. Keep the rectangular section as long as possible before transitioning.
A: Lower at high speed, because efficiency falls as airflow rises. At low speed the 2,000 m³/h size reaches 83.4% temperature efficiency, which is comparable with the residential sizes.
A: Where the zones share a duct route and the same operating schedule, yes, and the duct loss becomes the deciding factor. Where zones need independent control or different schedules, separate units are usually the better answer.
The two large sizes in the DC series deliver 1,500 and 2,000 m³/h against 180 and 200 Pa of external static pressure, through 346 × 326 mm rectangular spigots. Both use full DC motors on the supply and exhaust side, and both require a PVC condensate drain because of the air volume they move.
These sizes exist for spaces where ventilation load is set by occupancy rather than by floor area: restaurant floors, gyms, assembly halls, open-plan office floors and retail. In those spaces the duct run is long, the fittings are many, and the available static pressure decides whether the design airflow actually arrives at the diffuser. A unit rated at 2,000 m³/h with no pressure left is a 1,400 m³/h unit in practice.
Heat recovery at this scale is not a rounding error. At 2,000 m³/h with a 25 K temperature difference, the untreated ventilation load is around 16.8 kW; at the 83.4% low-speed efficiency of the 2,000 m³/h size, the residual load falls to about 2.8 kW. That difference is what separates a space that meets its ventilation requirement from a space that meets it and still keeps the plant size down.
| Item | HRV-D1500(B) | HRV-D2000(B) |
|---|---|---|
| Airflow (m³/h) | 1,500 | 2,000 |
| Input power H/M/L (W) | 680 / 320 / 200 | 950 / 500 / 230 |
| External static pressure (Pa) | 180 | 200 |
| Temperature efficiency H/M/L (%) | 75.5 / 78.6 / 80.2 | 77.2 / 79.5 / 83.4 |
| Enthalpy efficiency H/M/L (%) | 69.4 / 71.2 / 74.8 | 74.7 / 77.0 / 80.6 |
| Current (A) | 3.8 | 5.7 |
| Sound pressure H/M/L dB(A) at 1.5 m | 51.5 / 46.5 / 41.5 | 53 / 48.5 / 42.5 |
| Sound power (dB) | 69 | 70 |
| Dimensions L × W × H (mm) | 1740 × 1375 × 615 | 1811 × 1575 × 685 |
| Net / gross weight (kg) | 181.5 / 213 | 208.5 / 245 |
| Duct spigot | 346 × 326 mm | 346 × 326 mm |
A 2,000 m³/h unit is only as good as the duct system attached to it. The 346 × 326 mm spigot carries roughly 0.48 m² of face area, so the trunk velocity at 2,000 m³/h sits near 1.2 m/s at the spigot itself — comfortable, and the reason the rectangular connection is worth using rather than reducing to round immediately.
The 200 Pa figure is the budget for everything downstream: duct, elbows, tees, silencers, fire dampers, grilles and the diffusers themselves. A restaurant floor with a long run and several branch take-offs will consume most of it. Two practical rules follow. First, calculate the pressure loss before fixing the model, not after. Second, if silencers are added for acoustic reasons, they consume static pressure too and the size may need to move up.
Where the calculated loss exceeds the available pressure, the answer is usually duct sizing rather than a bigger unit. Increasing the trunk from 346 × 326 to the next size up drops velocity and loss faster than moving to a larger model increases available pressure.
Both large sizes require a PVC condensate drain. That is a design requirement, not an option: at these air volumes the moisture removed from the exhaust stream has to go somewhere, and the unit is normally installed in a plant room or a service bulkhead where a drain route exists.
The casing is 615 mm on the 1,500 m³/h size and 685 mm on the 2,000 m³/h size, with net weights of 181.5 and 208.5 kg. These are plant room or bulkhead units, not ceiling void units. Two people cannot lift them, the structure needs to be checked, and access for filter service has to be designed in from the start.
Efficiency on this series falls as airflow rises, which is why the large sizes show lower figures than the residential ones. At 1,500 m³/h the temperature efficiency is 75.5% at high speed, 78.6% at medium and 80.2% at low. At 2,000 m³/h it is 77.2%, 79.5% and 83.4%.
The practical consequence is that the last 25% of airflow costs disproportionately. Where a space can be served at 1,500 m³/h instead of 2,000 m³/h, both the efficiency and the fan power improve. Where 2,000 m³/h is genuinely required, the low-speed figure of 83.4% is the one to use in the energy calculation, provided the design allows low-speed operation as the normal condition.
| Model | Airflow | Input power (H/M/L) | Temp. efficiency (H/M/L) | Enthalpy efficiency (H/M/L) | Current | External static pressure | Sound pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; airflow and other single values are measured at high speed. Efficiency figures are measured with the standard G4 filter. The specification table is identical across all versions of this product page.
A: 2,000 m³/h on the HRV-D2000(B), rated against 200 Pa external static pressure.
A: It depends on the run. 200 Pa has to cover duct, elbows, silencers, dampers and grilles. Calculate the loss first; where it exceeds the available pressure, increase the duct size before moving to a larger model.
A: Yes. Both the 1,500 and 2,000 m³/h sizes require a PVC condensate drain. The 200 to 1,000 m³/h sizes do not.
A: Not normally. Casing depth is 615 mm and 685 mm with net weights of 181.5 and 208.5 kg. These are plant room or service bulkhead units, and the structure must be checked.
A: 346 × 326 mm rectangular spigots on both sizes. Keep the rectangular section as long as possible before transitioning.
A: Lower at high speed, because efficiency falls as airflow rises. At low speed the 2,000 m³/h size reaches 83.4% temperature efficiency, which is comparable with the residential sizes.
A: Where the zones share a duct route and the same operating schedule, yes, and the duct loss becomes the deciding factor. Where zones need independent control or different schedules, separate units are usually the better answer.