Commercial ventilation schedules typically list many different spaces with different airflow requirements: guest rooms, meeting rooms, classrooms, restaurant floors and apartments. Specifying a separate product family for each one multiplies the number of controllers, filters and spare parts carried on the project. The DC Series covers the entire schedule from a single platform, with eight ceiling-mounted sizes spanning 200 to 2,000 m³/h and one control and filter architecture across the full range.
The mapping is straightforward. Sizes from 200 to 500 m³/h serve hotel suites, meeting rooms and apartments, and three of them fit a 272 mm ceiling void. Sizes from 800 to 1,000 m³/h cover offices and classrooms where occupancy is dense and CO2 control pays back fastest. The 1,500 and 2,000 m³/h models handle open-plan floors, restaurants and gyms, where high footfall and odour extraction dominate the design.
Filtration and controls scale with the space rather than the model. G4 filters are standard on both air streams for offices, retail, restaurants and hotels; F7 on the supply side and M5 on the exhaust side meet tighter EU air-quality specifications for schools, clinics and premium offices. Sound pressure down to 24.5 dB(A) at low speed keeps guest rooms and classrooms within acoustic limits, and the same unit that runs on a wired controller in an apartment can be handed to a BMS in an office tower.
| Space | Typical airflow | Models | Notes |
|---|---|---|---|
| Hotel guest room, suite | 200–300 m³/h | HRV-D200, D300 | 272 mm casing; low speed 25.5–30 dB(A) |
| Meeting room | 200–500 m³/h | HRV-D200 to D500 | CO2 option suits variable occupancy |
| Apartment, villa | 200–400 m³/h | HRV-D200, D300, D400 | 272 mm casing, no drain required |
| Office, business park | 800–1,000 m³/h | HRV-D800, D1000 | CO2 control plus BMS gateway |
| Classroom, training room | 800–1,000 m³/h | HRV-D800, D1000 | F7 supply filter where air-quality class requires |
| Clinic, healthcare area | Per project calculation | HRV-D400 to D1000 | F7 supply plus M5 exhaust; balanced supply and exhaust |
| Restaurant, retail floor | 1,500–2,000 m³/h | HRV-D1500, D2000 | PVC drain required; odour extraction |
| Gym, open-plan floor | 1,500–2,000 m³/h | HRV-D1500, D2000 | PVC drain required; high occupancy |
Sizing always follows the project's ventilation calculation. The mapping above reflects common practice across these building types and is not a substitute for design.
The standard G4 configuration suits most commercial projects: offices, retail, restaurants and hotels where the goal is energy-efficient ventilation with low pressure drop and the highest heat recovery figures. For projects quoting EU air-quality classes — schools, healthcare, premium offices — the optional F7 filter on the supply side and M5 on the exhaust side raise filtration grade while the DC fans absorb the extra static pressure. Efficiency data for both configurations is published in the engineering manual, so consultants can model either option without derating guesswork.
A mixed-use building usually needs three or four different airflow sizes at once. Because all eight models share the same controller range, the same filter grades and the same gateway options, the project carries one spare-parts list instead of three. Commissioning follows the same sequence on every unit, and facility staff learn one interface rather than one per space type. On phased handovers, units can be added floor by floor without changing the control architecture.
| Model | Airflow | Input power (H/M/L) | Temp. efficiency (H/M/L) | Enthalpy efficiency (H/M/L) | Current | External static pressure | Sound pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; single values measured at high speed. Sound pressure measured 1.5 m below the unit. Efficiency figures with the standard G4 filter; F7 plus M5 data published in the engineering manual. Operating range -7 °C to +43 °C, indoor humidity below 80%. Only HRV-D1500 and D2000 require a PVC drain. Power supply 220–240 V, single-phase, 50 Hz on all sizes.
Q: How do I choose the right size?
A: Start from the project's ventilation calculation, then map to the nearest model. 200–500 m³/h covers suites, meeting rooms and apartments; 800–1,000 m³/h covers offices and classrooms; 1,500–2,000 m³/h covers open-plan floors, restaurants and gyms.
Q: Which model suits a hotel guest room?
A: HRV-D200 or D300, both 272 mm deep, running at low speed with sound pressure of 25.5 to 30 dB(A). Neither needs a condensate drain, which keeps the corridor ceiling simple.
Q: What airflow does a classroom need?
A: Classroom sizing follows the occupancy calculation, and in practice the 800–1,000 m³/h models cover most teaching spaces. Where an EU air-quality class applies, specify the F7 supply filter.
Q: Should I specify G4 or F7 plus M5?
A: G4 standard for offices, retail, restaurants and hotels. F7 supply and M5 exhaust where the project quotes an EU air-quality class, such as schools, clinics and premium offices.
Q: Do restaurant projects need the drain?
A: The 1,500 and 2,000 m³/h models used on restaurant floors do require a PVC drain connection with slope and trap. Sizes up to 1,000 m³/h need no drain at all.
Q: Can one unit serve several rooms?
A: Yes, where the duct design allows it and the airflow matches. Ducted distribution from one unit usually needs a larger size and careful static pressure budgeting; individual units per room simplify balancing and zoning.
Q: What if the calculated airflow falls between two models?
A: Take the larger model and set the design point at medium speed. Efficiency is higher at lower speed, and the spare capacity covers filter loading and future changes of use.
Commercial ventilation schedules typically list many different spaces with different airflow requirements: guest rooms, meeting rooms, classrooms, restaurant floors and apartments. Specifying a separate product family for each one multiplies the number of controllers, filters and spare parts carried on the project. The DC Series covers the entire schedule from a single platform, with eight ceiling-mounted sizes spanning 200 to 2,000 m³/h and one control and filter architecture across the full range.
The mapping is straightforward. Sizes from 200 to 500 m³/h serve hotel suites, meeting rooms and apartments, and three of them fit a 272 mm ceiling void. Sizes from 800 to 1,000 m³/h cover offices and classrooms where occupancy is dense and CO2 control pays back fastest. The 1,500 and 2,000 m³/h models handle open-plan floors, restaurants and gyms, where high footfall and odour extraction dominate the design.
Filtration and controls scale with the space rather than the model. G4 filters are standard on both air streams for offices, retail, restaurants and hotels; F7 on the supply side and M5 on the exhaust side meet tighter EU air-quality specifications for schools, clinics and premium offices. Sound pressure down to 24.5 dB(A) at low speed keeps guest rooms and classrooms within acoustic limits, and the same unit that runs on a wired controller in an apartment can be handed to a BMS in an office tower.
| Space | Typical airflow | Models | Notes |
|---|---|---|---|
| Hotel guest room, suite | 200–300 m³/h | HRV-D200, D300 | 272 mm casing; low speed 25.5–30 dB(A) |
| Meeting room | 200–500 m³/h | HRV-D200 to D500 | CO2 option suits variable occupancy |
| Apartment, villa | 200–400 m³/h | HRV-D200, D300, D400 | 272 mm casing, no drain required |
| Office, business park | 800–1,000 m³/h | HRV-D800, D1000 | CO2 control plus BMS gateway |
| Classroom, training room | 800–1,000 m³/h | HRV-D800, D1000 | F7 supply filter where air-quality class requires |
| Clinic, healthcare area | Per project calculation | HRV-D400 to D1000 | F7 supply plus M5 exhaust; balanced supply and exhaust |
| Restaurant, retail floor | 1,500–2,000 m³/h | HRV-D1500, D2000 | PVC drain required; odour extraction |
| Gym, open-plan floor | 1,500–2,000 m³/h | HRV-D1500, D2000 | PVC drain required; high occupancy |
Sizing always follows the project's ventilation calculation. The mapping above reflects common practice across these building types and is not a substitute for design.
The standard G4 configuration suits most commercial projects: offices, retail, restaurants and hotels where the goal is energy-efficient ventilation with low pressure drop and the highest heat recovery figures. For projects quoting EU air-quality classes — schools, healthcare, premium offices — the optional F7 filter on the supply side and M5 on the exhaust side raise filtration grade while the DC fans absorb the extra static pressure. Efficiency data for both configurations is published in the engineering manual, so consultants can model either option without derating guesswork.
A mixed-use building usually needs three or four different airflow sizes at once. Because all eight models share the same controller range, the same filter grades and the same gateway options, the project carries one spare-parts list instead of three. Commissioning follows the same sequence on every unit, and facility staff learn one interface rather than one per space type. On phased handovers, units can be added floor by floor without changing the control architecture.
| Model | Airflow | Input power (H/M/L) | Temp. efficiency (H/M/L) | Enthalpy efficiency (H/M/L) | Current | External static pressure | Sound pressure (H/M/L) |
|---|---|---|---|---|---|---|---|
| HRV-D200(B) | 200 m³/h | 70/45/25 W | 79.5/81.1/83.5% | 75.0/77.5/79.6% | 0.64 A | 100 Pa | 33/29.5/25.5 dB(A) |
| HRV-D300(B) | 300 m³/h | 100/55/35 W | 75.5/78.8/82.5% | 72.1/75.0/79.3% | 0.84 A | 90 Pa | 36.5/33.5/30 dB(A) |
| HRV-D400(B) | 400 m³/h | 110/70/40 W | 77.7/79.0/81.3% | 73.5/75.3/78.0% | 0.97 A | 100 Pa | 36.5/32/28 dB(A) |
| HRV-D500(B) | 500 m³/h | 150/95/50 W | 80.6/82.2/85.5% | 74.0/76.6/80.5% | 1.2 A | 90 Pa | 36/30.5/24.5 dB(A) |
| HRV-D800(B) | 800 m³/h | 320/170/80 W | 78.7/82.1/86.8% | 72.3/75.4/79.0% | 2.4 A | 140 Pa | 42/39/34 dB(A) |
| HRV-D1000(B) | 1,000 m³/h | 380/210/100 W | 82.8/84.0/87.4% | 76.0/76.0/80.1% | 2.9 A | 160 Pa | 44/39/33.5 dB(A) |
| HRV-D1500(B) | 1,500 m³/h | 680/320/200 W | 75.5/78.6/80.2% | 69.4/71.2/74.8% | 3.8 A | 180 Pa | 51.5/46.5/41.5 dB(A) |
| HRV-D2000(B) | 2,000 m³/h | 950/500/230 W | 77.2/79.5/83.4% | 74.7/77.0/80.6% | 5.7 A | 200 Pa | 53/48.5/42.5 dB(A) |
Notes: three fan speeds on all models; single values measured at high speed. Sound pressure measured 1.5 m below the unit. Efficiency figures with the standard G4 filter; F7 plus M5 data published in the engineering manual. Operating range -7 °C to +43 °C, indoor humidity below 80%. Only HRV-D1500 and D2000 require a PVC drain. Power supply 220–240 V, single-phase, 50 Hz on all sizes.
Q: How do I choose the right size?
A: Start from the project's ventilation calculation, then map to the nearest model. 200–500 m³/h covers suites, meeting rooms and apartments; 800–1,000 m³/h covers offices and classrooms; 1,500–2,000 m³/h covers open-plan floors, restaurants and gyms.
Q: Which model suits a hotel guest room?
A: HRV-D200 or D300, both 272 mm deep, running at low speed with sound pressure of 25.5 to 30 dB(A). Neither needs a condensate drain, which keeps the corridor ceiling simple.
Q: What airflow does a classroom need?
A: Classroom sizing follows the occupancy calculation, and in practice the 800–1,000 m³/h models cover most teaching spaces. Where an EU air-quality class applies, specify the F7 supply filter.
Q: Should I specify G4 or F7 plus M5?
A: G4 standard for offices, retail, restaurants and hotels. F7 supply and M5 exhaust where the project quotes an EU air-quality class, such as schools, clinics and premium offices.
Q: Do restaurant projects need the drain?
A: The 1,500 and 2,000 m³/h models used on restaurant floors do require a PVC drain connection with slope and trap. Sizes up to 1,000 m³/h need no drain at all.
Q: Can one unit serve several rooms?
A: Yes, where the duct design allows it and the airflow matches. Ducted distribution from one unit usually needs a larger size and careful static pressure budgeting; individual units per room simplify balancing and zoning.
Q: What if the calculated airflow falls between two models?
A: Take the larger model and set the design point at medium speed. Efficiency is higher at lower speed, and the spare capacity covers filter loading and future changes of use.